All Categories
    Menu Close

    How to Size a Three-Phase Autotransformer?

    A three-phase autotransformer should be sized according to the maximum apparent power delivered to the connected load. The basic calculation uses the required output line-to-line voltage and the maximum simultaneous output line current.

    Calculate the required three-phase load capacity using:

    kVA = √3 × Output Voltage × Maximum Output Current ÷ 1000

    Select a purpose-built autotransformer with a catalog load rating equal to or greater than the calculated result. Then verify motor starting, load imbalance, harmonics, duty cycle, ambient temperature, altitude, wiring configuration and voltage-drop requirements.

    PowerHome offers three-phase autotransformers for fixed industrial voltage matching. Standard and custom configurations can be used to match common three-phase supply and equipment voltages, including 200V, 220V, 230V, 240V, 380V, 400V, 415V and 480V systems.

    1. What Information Is Needed Before Sizing?

    Before calculating the required kVA, collect the electrical and operating data for both the available power supply and the connected equipment. Use the measured site voltage and equipment nameplate values whenever possible.

    These details determine the required voltage ratio, load capacity, wiring configuration and operating conditions.

     Category  Parameter  Information Required
     Electrical Data  Site supply voltage  Measured input line-to-line voltage
     Required load voltage  Equipment-rated line-to-line voltage
     Maximum load current  Maximum simultaneous output line current
     Phase  Confirm a three-phase supply and three-phase load
     Frequency  Confirm whether the system operates at 50 Hz or 60 Hz
     Load and Wiring  Load type  Motor, heater, VFD, rectifier, welder or mixed load
     Starting method  Direct-on-line, star-delta, soft starter or VFD
     Wiring system  Three-wire or four-wire; delta or wye
     Neutral requirement  Whether the connected equipment requires a neutral conductor
     Duty cycle  Continuous, intermittent or short-time operation
     Installation  Installation environment  Ambient temperature, altitude, humidity, ventilation and enclosure requirements

    For motor-driven equipment, also provide the motor rated power, full-load current, power factor, efficiency, starting current and starting method.

    When several loads share one autotransformer, identify which devices will operate or start at the same time. The transformer should be sized for the maximum simultaneous load rather than automatically adding every nameplate rating.

    A clear equipment nameplate photo and the measured site voltage are usually the most useful starting points.

    2. How to Calculate Three-Phase Load kVA

    For a balanced or nearly balanced three-phase load, calculate the required apparent power using the equipment's required output line-to-line voltage and maximum simultaneous output line current.

    Three-Phase Load Capacity
    Sload = (√3 × Voutput × Ioutput) ÷ 1000

    Where:

    • Sload is the required load capacity in kVA.
    • Voutput is the required output line-to-line voltage in volts.
    • Ioutput is the maximum simultaneous output line current in amperes.
    • √3 is approximately 1.732.
     Use for the Calculation  Do Not Substitute
     Required output line-to-line voltage  Input or site supply voltage
     Maximum simultaneous output current  Current of only one device when several loads operate together
     Three-phase kVA formula  Single-phase VA or kVA formula
     Motor nameplate full-load current when available  Motor horsepower or kW alone

    Use the voltage required by the connected equipment, not the supply voltage, when calculating output load kVA. The current must represent the maximum load operating at the same time.

    The formula assumes a balanced or nearly balanced three-phase load. If the system includes substantial single-phase branches, check the current on each phase separately.

    When a motor nameplate provides only kW or horsepower, motor efficiency and power factor must also be considered. Whenever possible, use the motor's nameplate full-load current as the primary sizing value.

    3. Worked Example: Sizing a 480V to 400V Autotransformer

    Assume the following operating requirements:

    Input Supply 480V Three-Phase
    Required Output 400V Three-Phase
    Maximum Output Current 100A

    First, calculate the required three-phase load capacity:

    Load kVA Calculation
    Sload = (1.732 × 400 × 100) ÷ 1000 = 69.3 kVA

    For a purpose-built autotransformer rated by load or throughput kVA, select a catalog rating equal to or greater than 69.3 kVA.

    Selection Result

    • Calculated load: 69.3 kVA
    • Minimum standard catalog size: 75 kVA
    • Voltage ratio: 480V input to 400V output
    • Phase: Three-phase
    • Final checks: Load type, starting current, duty cycle, harmonics, ambient conditions and allowable voltage drop

    In this example, the calculated load is 69.3 kVA, so the next suitable standard capacity is 75 kVA. A 480V to 400V three-phase autotransformer should therefore have a catalog load rating of at least 75 kVA, subject to confirmation of motor starting current, harmonics, duty cycle, ambient conditions and allowable voltage drop.

    The ideal input current can also be estimated:

    Estimated Input Current
    Iinput = (69.3 × 1000) ÷ (1.732 × 480) ≈ 83.3A

    This input-current value is an ideal calculation and does not include transformer losses or operating tolerances.

    Final conductor sizing and overcurrent protection should be based on the transformer nameplate currents, manufacturer instructions and applicable electrical requirements.

    4. Load kVA vs. Winding kVA

    Key selection rule: For a purpose-built autotransformer rated by load or throughput kVA, compare the calculated load kVA directly with the catalog load rating. Do not select the transformer from the lower winding-kVA value unless the manufacturer explicitly rates the product that way.

    Load kVA

    Load kVA is the total apparent power delivered to the connected equipment. In the 480V-to-400V example:

    Sload = 69.3 kVA

    For a purpose-built autotransformer rated by load or throughput kVA, 69.3 kVA is the value used to select the finished-product capacity.

    Winding kVA

    An autotransformer transfers part of its power conductively through the shared winding connection. Only the voltage difference is transformed magnetically.

    The approximate winding kVA can be calculated as:

    Equivalent Winding Capacity
    Swinding = Sload × (VH − VL) ÷ VH

    Where VH is the higher voltage and VL is the lower voltage.

    For a 480V-to-400V autotransformer supplying a 69.3 kVA load:

    Swinding = 69.3 × (480 − 400) ÷ 480 = 11.55 kVA

    The 11.55 kVA value represents the approximate portion of power transformed magnetically. It does not mean that an 11.55 kVA catalog autotransformer can supply a 69.3 kVA load.

     Rating Term  Meaning  How It Is Used for Selection
     Load kVA  Total apparent power required by the connected load  Used to determine the required finished-product capacity
     Winding kVA  Portion of the power transformed magnetically  Used for transformer design or as a capacity reasonableness check
     Buck-boost nameplate kVA  Rating of an individual two-winding transformer  Use the manufacturer's dedicated buck-boost selection table
     Catalog load kVA  Maximum load capacity assigned to a purpose-built autotransformer  Compare directly with the calculated load kVA

     

    5. What Affects the Required Autotransformer kVA?

    Calculated load kVA is only the starting point. Motor starting, simultaneous loads, harmonics, phase imbalance, duty cycle and installation conditions may increase the required rating. A fixed safety margin should not be applied to every application.

    • Motor Loads: For motor-driven equipment, size the autotransformer using the motor nameplate full-load current rather than horsepower or kW alone. Also confirm the starting method, starting current, acceleration time, starts per hour and allowable voltage drop. For example, a 30 kVA 480V to 380V three-phase autotransformer may match a 480V supply to compatible 380V equipment, provided the motor current, frequency and starting requirements are verified.
    • Multiple Connected Loads: Base the calculation on the maximum load operating at the same time. Consider the largest motor, simultaneous motor starts and the maximum starting combination. Staggered starting may reduce the required capacity.
    • VFDs and Nonlinear Loads: For VFD applications, provide the input current, voltage range, rated power and installation position. VFDs, rectifiers and UPS systems can create harmonic current and additional heating, so suitability and derating should be confirmed.
    • Unbalanced Three-Phase Loads: The standard three-phase kVA formula assumes a balanced load. For systems with substantial single-phase loads, check each phase current, neutral current and maximum phase loading separately.
    • Duty Cycle and Environment: Continuous operation, high ambient temperature, altitude, poor ventilation, humidity and enclosure conditions may require a larger rating or derating.
    • Frequency Compatibility: An autotransformer changes voltage but not frequency or phase. For example, 480V 60Hz converted to 400V remains 400V 60Hz. Equipment requiring 50Hz may need a frequency converter.

    6. Three-Phase Autotransformer Selection Process

    Follow these steps to confirm the electrical requirements, calculate the load and select an appropriate catalog rating.

    1. Confirm the measured site supply voltage.
    2. Confirm the equipment's required operating voltage.
    3. Confirm the phase, frequency and wiring configuration.
    4. Calculate the maximum simultaneous three-phase load kVA.
    5. Check motor starting, VFDs, rectifiers and harmonic-producing loads.
    6. Check phase balance, neutral requirements and maximum phase current.
    7. Select the next verified catalog load rating equal to or greater than the calculated requirement.
    8. Confirm the enclosure, cooling, terminals, conductors and protection requirements.
    Information Needed for Model Selection

    To confirm the correct three-phase autotransformer size, provide the input and output voltage, maximum output current, frequency, load type, starting method, wiring and neutral requirements, duty cycle, ambient conditions, and preferred enclosure and cooling method.

    Comments
    Write a comment Close
    *