All Categories
    Menu Close

    How to Size a Frequency Converter?

    Choosing a frequency converter requires more than matching its kVA rating to the equipment wattage. The converter must match the required voltage, frequency and phase while providing enough capacity for running current, power factor, startup demand and continuous operation. This guide explains the main sizing steps for imported equipment, industrial machinery, motors, test systems and 400Hz loads.

    What Does a Frequency Converter Do?

    A frequency converter supplies controlled AC power at a different frequency, such as 50Hz to 60Hz, 60Hz to 50Hz, or 50/60Hz to and from 400Hz. Depending on the configuration, it may also change or regulate the output voltage.

    PowerHome offers single-phase and three-phase frequency converters with adjustable output voltage, pure sine wave output and selectable frequencies.

    Step 1: Check the Equipment Nameplate

    Record the equipment specifications before calculating capacity.

    Required Information

    Example

    Why It Matters

    Phase

    Single phase or three phase

    Determines the required output configuration.

    Rated voltage

    120V, 230V, 400V or 480V

    Must match the converter output voltage.

    Rated frequency

    50Hz, 60Hz or 400Hz

    Determines the required output frequency.

    Rated current or power

    8A or 1.5kW

    Used to calculate the running load.

    Power factor

    0.8

    Required when converting kW to kVA.

    Starting method and duty

    Direct-on-line, soft starter, VFD; continuous or intermittent

    Affects startup demand and operating margin.

    The converter input must match the available site supply, while its output phase, voltage and frequency must match the equipment. For example, equipment marked “3PH, 400V, 50Hz” requires three-phase 400V 50Hz output.

    Step 2: Calculate the Running Load in kVA

    Frequency converters are normally rated in kVA. Use the equipment voltage and current whenever available.

    Single-Phase Load

    Running kVA = Voltage × Current ÷ 1,000

    For a 230V load drawing 8A:

    230 × 8 ÷ 1,000 = 1.84kVA

    Three-Phase Load

    Running kVA = 1.732 × Line Voltage × Line Current ÷ 1,000

    For a 400V three-phase load drawing 18A:

    1.732 × 400 × 18 ÷ 1,000 = 12.47kVA

    When Only kW Is Listed

    Running kVA = kW ÷ Power Factor

    An 8kW load with a power factor of 0.8 requires 10kVA. Do not assume that kW and kVA are equal unless the power factor is 1.0.

    Step 3: Allow for Continuous Operation

    For stable continuous operation, a practical target is to keep the load at about 70% to 80% of the converter rating.

    Minimum Converter Capacity = Running kVA ÷ 0.8

    For the 12.47kVA example:

    12.47 ÷ 0.8 = 15.59kVA

    Select the next suitable catalog size. In this case, a 20kVA converter provides more appropriate continuous-duty capacity than a 15kVA unit.

    Step 4: Account for Starting and Inrush Current

    Motors, pumps, compressors, transformers and other inductive loads may draw much more current during startup. The required capacity depends on the starting method, mechanical load, acceleration time, startup frequency and actual inrush current.

    Load Type

    Preliminary Allowance

    Sizing Note

    Resistive heater

    1.25 × running kVA

    Usually has low startup current.

    Electronic or laboratory equipment

    1.25–1.5 × running kVA

    Allow for internal power supplies and short current peaks.

    Small motor with a light load

    1.5–2 × running kVA

    Use only when actual starting current is unavailable.

    Pump or compressor

    2–3 × running kVA or higher

    Heavy loading or direct starting may require more capacity.

    Transformer or heavy machinery

    Use actual startup data

    Confirm inrush current, duration and simultaneous demand.

    These multipliers are preliminary only. Measured or manufacturer-specified starting current is more reliable.

    Motor Starting Example

    Starting kVA = 1.732 × Voltage × Starting Current ÷ 1,000

    A 400V motor drawing 7A while running and 32A during startup requires:

    Running load: 1.732 × 400 × 7 ÷ 1,000 = 4.85kVA
    Starting load: 1.732 × 400 × 32 ÷ 1,000 = 22.17kVA

    The converter must support both the continuous load and the short startup demand. Overload capability should not replace proper sizing.

    Step 5: Size for Multiple Loads

    Calculate the maximum demand that will occur at the same time rather than adding every possible startup current.

    Required Capacity = Simultaneous Running kVA + Largest Expected Starting Demand + Operating Margin

    For loads of 1.2kVA, 2kVA and 1kVA, plus 2kVA of additional motor starting demand, the peak requirement is 6.2kVA. After allowing operating margin, a 10kVA converter may be more suitable than a 5kVA model.

    Step 6: Check Output-Frequency Derating

    Some converters provide full rated capacity only within a specified frequency range. For applicable PowerHome models, full capacity is available up to 120Hz, while output capacity is reduced above 120Hz. At 400Hz, usable capacity may be approximately 50% of the nameplate rating.

    For a continuous 4kVA, 400Hz load:

    Required Nameplate Capacity = 4kVA ÷ 0.5 = 8kVA

    The next suitable size would be 10kVA. Always verify the derating specified for the selected model.

    Step 7: Match Voltage, Phase and Wiring

    Capacity alone does not confirm compatibility. Single-phase converters are commonly used for appliances, laboratory instruments and small machines, while three-phase models are used for industrial machinery, CNC equipment, pumps, compressors and production systems.

    Before ordering, confirm the input voltage and phase, Wye or Delta wiring, neutral availability, required output voltage and frequency, and maximum load current.

    Quick Frequency Converter Selection Table

    Continuous Load

    Suggested Size

    Typical Applications

    Recommended Converter

    Up to 0.4kVA

    500VA

    Small electronics and instruments

    500VA/1000VA Single Phase Frequency Converter

    Up to 0.8kVA

    1kVA

    Imported appliances and laboratory equipment

    500VA/1000VA Single Phase Frequency Converter

    Up to 1.6kVA

    2kVA

    Commercial equipment and test instruments

    2kVA/3kVA Single Phase Frequency Converter

    Up to 2.4kVA

    3kVA

    Small machinery and multiple instruments

    2kVA/3kVA Single Phase Frequency Converter

    Up to 4kVA

    5kVA

    Test benches, heaters and light-duty motors

    5kVA Single Phase Frequency Converter

    Up to 8kVA

    10kVA

    Large equipment and industrial test systems

    10kVA Single Phase Frequency Converter

    Up to 12kVA

    15kVA

    Medium industrial machinery and test benches

    15kVA/20kVA Three Phase Frequency Converter

    Up to 16kVA

    20kVA

    Production machinery and industrial testing

    15kVA/20kVA Three Phase Frequency Converter

    Up to 24kVA

    30kVA

    CNC equipment and centralized testing

    30kVA/45kVA/60kVA Three Phase Frequency Converter

    Up to 36kVA

    45kVA

    Industrial pumps and production machinery

    30kVA/45kVA/60kVA Three Phase Frequency Converter

    Up to 48kVA

    60kVA

    Large industrial machines and production systems

    30kVA/45kVA/60kVA Three Phase Frequency Converter

    Up to 60kVA

    75kVA

    High-current manufacturing equipment

    75kVA/100kVA Three Phase Frequency Converter

    Up to 80kVA

    100kVA

    Plant-level testing and manufacturing systems

    75kVA/100kVA Three Phase Frequency Converter

    Up to 120kVA

    150kVA

    Heavy industrial machinery and production lines

    150kVA/200kVA Three Phase Frequency Converter

    Up to 160kVA

    200kVA

    Large production lines and custom projects

    150kVA/200kVA Three Phase Frequency Converter

    The table assumes a continuous load of approximately 80% of the converter rating. Motors, pumps, compressors, transformers and other high-inrush loads may require additional capacity.

    Common Sizing Mistakes

    • Selecting by watts alone: Watts do not account for power factor, apparent power or startup current.
    • Matching converter kVA directly to running kVA: Continuous loads require operating margin.
    • Ignoring startup current: A converter may run a motor normally but shut down during starting.
    • Matching frequency but not voltage or phase: All three output parameters must match the equipment.
    • Confusing a frequency converter with a VFD: A VFD primarily controls motor speed, while a static frequency converter supplies controlled AC power to motors or mixed loads.
    • Ignoring 400Hz derating: Apply the high-frequency capacity reduction specified for the model.

    Final Selection Checklist

    • Available input voltage, phase and wiring configuration
    • Required output voltage, phase and frequency
    • Total simultaneous running current or kVA
    • Power factor, starting current and startup duration
    • Continuous or intermittent duty
    • Ambient conditions and required operating margin
    • 400Hz derating, when applicable
    • Future expansion requirements

    Find the Right Frequency Converter

    Explore PowerHome frequency converters for 50Hz, 60Hz and 400Hz applications. Single-phase and three-phase models are available for imported equipment, industrial testing, manufacturing systems and custom projects.

    Shop Frequency Converters

    Comments
    Write a comment Close
    *